Overview of Microgrid Results

Microgrid Name Generation Bus Minimum 1 hr Load (kW) Average 1 hr Load (kW) Average Daytime 1 hr Load (kW) Maximum 1 hr Load (kW) Minimum 1 hr Critical Load (kW) Average 1 hr Critical Load (kW) Average Daytime 1 hr Critical Load (kW) Maximum 1 hr Critical Load (kW) Existing Fossil Generation (kW) New Fossil Generation (kW) Existing Solar (kW) New Solar (kW) Existing Battery Power (kW) Existing Battery Energy Storage (kWh) New Battery Power (kW) New Battery Energy Storage (kWh) Existing Wind (kW) New Wind (kW) Total Generation on Microgrid (kW) Renewable Generation (% of Annual kWh) Emissions (Yr 1 Tons CO2) Emissions Reduction (Yr 1 % CO2) Average Outage Survived (h) O+M Costs (Yr 1 $ before tax) CapEx ($) CapEx after Tax Incentives ($) Net Present Value ($)
mg0 634 789 1,493 1,913 2,713 60 178 248 306 0 890 440 1,223 79 307 0 0 0 0 2,592 17 5,800 7 8,760 82,313 2,957,194 2,076,464 1,174,763
mg1 675 789 1,493 1,913 2,713 211 403 498 713 0 922 800 2,852 0 0 112 147 0 0 4,686 37 4,452 26 8,760 117,607 5,971,474 3,911,057 1,470,672
mg2 684 789 1,493 1,913 2,713 317 551 684 909 81 844 0 3,637 20 100 89 43 0 0 4,671 37 4,469 32 8,760 117,628 7,006,711 4,390,308 2,145,073
mg3 646 789 1,493 1,913 2,713 25 139 216 385 0 872 0 1,538 40 10 40 37 0 0 2,446 16 5,868 11 8,760 78,821 3,629,368 2,525,887 1,305,561
Summary None 789 1,493 1,913 2,713 613 1,271 1,646 2,313 81 3,528 1,240 9,250 139 417 241 227 0 0 14,395 27 20,589 19 8,760 396,369 19,564,747 12,903,716 6,096,069

Report Generated

2024-04-03 20:00:05.862625

User Warnings

Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.
Pre-existing battery battery_684_existing will not be utilized to support loads in microgrid mg2.

Distribution Upgrades needed to create Microgrids

Microgrid Location Recommended Upgrade Cost Estimate ($)
mg0 mg0 Microgrid Design 100,000
mg0 mg0 Microgrid Controls 100,000
mg0 632633 SCADA disconnect switch 50,000
mg0 634a_data_center AMI disconnect meter 300
mg0 634b_radar AMI disconnect meter 300
mg0 634c_atc_tower AMI disconnect meter 300
mg1 mg1 Microgrid Design 100,000
mg1 mg1 Microgrid Controls 100,000
mg1 671692 SCADA disconnect switch 50,000
mg1 675a_hospital 3-phase relay 20,000
mg1 675b_residential1 3-phase relay 20,000
mg1 675c_residential1 3-phase relay 20,000
mg1 692_warehouse2 3-phase relay 20,000
mg2 mg2 Microgrid Design 100,000
mg2 mg2 Microgrid Controls 100,000
mg2 671684 SCADA disconnect switch 50,000
mg2 684_command_center AMI disconnect meter 300
mg2 652_residential AMI disconnect meter 300
mg2 611_runway AMI disconnect meter 300
mg3 mg3 Microgrid Design 100,000
mg3 mg3 Microgrid Controls 100,000
mg3 632645 SCADA disconnect switch 50,000
mg3 645_hangar AMI disconnect meter 300
mg3 646_office AMI disconnect meter 300

Description